Condition:NEW | Type:Water-Cooled | Place of Origin:Shandong China (Mainland) | Brand Name:MGREENBELT |
Model Number:MG-10W | Cooling Capability(kw):30KW | Voltage:3PH-220V/380V-50HZ/60HZ | Dimension(L*W*H):1170mm*710mm*1200mm |
Weight:430kgs | Certification:CE,ROHS,UL,ISO9001 | Warranty:14 Months | After-sales Service Provided:Engineers available to service machinery overseas |
Product type:Water Cooled Industrial Chiller | Compressor power:4.55KW*2 | Compressor:Sanyo/Copeland with hermetic scroll type | Applied temp:0-50 Degree C |
Refrigerant:R22(R134a,407c optional) | Expansion valve:EMERSON | Condenser:Shell and tube type | Evaporator:Stainless steel tank with coil/Shell and tube |
Shipping to your door:Accept | CE:Yes |
Water Chiller Unit/Water Cooled Industrial Chiller
Water Chiller Unit - Water Cooled Industrial Chiller Features:
1. Employing all new imported compressor, with longer terms of service.
2. High efficiency evaporator and cooling condenser in use, to help save no less than 30% of your power rates.
3. High precision, temperature control to save energy.
4. Complete with safety protection and error indication system.
Water Chiller Unit - Water Cooled Industrial Chiller Model:MG-10W
Specification model | Unit | MG-10W(D) |
Nominal cooling capacity | kcal/h | 25800 |
KW | 30 | |
Input power | KW | 9.85 |
Set temp. range | 0ºC~50ºC | |
Power supply | 3PH-380V-50HZ (200V/220V/415V-50HZ/60HZ) | |
Refrigerant | Type | R22/R134a/407c |
Type of control | Thermostatic expansion valve | |
Compressor | Type | Hermetic scroll |
Power(kw) | 4.55*2 | |
Condenser | Type | shell and tube |
Cooling water flow(m3/h) | 6.76 | |
Inlet and outlet pipe diameter(inch) | 1-1/2" | |
Evaporator | Type | Tank with coil/shell and tube |
Chilled fluid flow(m3/h) | 5.26 | |
Volume(L) | 200 | |
Inlet and outlet pipe diameter(inch) | 1-1/2" | |
Pump | Power(kw) | 0.75 |
Lift(m) | 20 | |
Dimension | Length(mm) | 1170 |
Wide(mm) | 710 | |
High(mm) | 1200 | |
Weight | kg | 430 |
Safety protection | Compressor over temperature,over current,high and low pressure,Phase sequence,phase-missing |
Water chiller unit:
Our main products:
Factory:
Water Cooled Chiller working princlple:
We need some questions to ask you:
1.What the flow you need?
2.What the in and out water temp you need?
3. Refrigerant use R22 OR R404A?
4.What voltage do you need?
Then we can choose the right chiller for you.
Packaging Detail:Standard wooden case |
Delivery Detail:Within two weeks after payment |