Mobile Small Transformer Oil Dewatering Dehydraion Purifier
Condition:New | Place of Origin:Chongqing China (Mainland) | Brand Name:YUNENG | Model Number:ZJA Series |
Usage:Transformer Oil | After-sales Service Provided:Engineers available to service machinery overseas | Function:Oil Filter | Structure:Vacuum Filter |
Material:Other |
Mobile Small Transformer Oil Dewatering Dehydraion Purifier
Dissolved gasses in transformer oil can cause arcing, corona discharges, and overheating--reducing the electrical efficiency.
Why purify transformer oil?
Dissolved gasses in transformer oil can cause arcing, corona discharges, and overheating--reducing the electrical efficiency and lifetime of the transformer. Likewise, water contamination at levels as low as 30 ppm (parts per million) can adversely affect the insulating strength of the oil. With ever-increasing standards for energy efficiency of power distribution transformers, the need to effectively degas will become even more important in the future. particles contamination will also affect the function of insulating oil. So we need to clean used transformer oil.
Application
ZJA Mobile Small Transformer Oil Dewatering Dehydraion Purifier is mainly used to improve the properties of insulation oil. It can remove trace water, gas, particulate matters etc. from the insulating oil effectively and rapidly so as to boost performance of transformers, circuit breakers, mutual inductors, cable and capacitors which has insulation system.ZJA series specialize in purifying branded oil, insulating oil of high voltage and super high voltage transformer. Additionally, it is suitable for treating low viscosity lubrication oil.
Item | Parameter | Type Unit | ZJA1.8KY | ZJA3KY | ZJA6KY | ZJA9KY | ZJA12KY | ZJA18KY | |
Technical parameter | Flow Rate | L/H | 1800 | 3000 | 6000 | 9000 | 12000 | 18000 | |
Working Vacuity | Pa | ≤80 | |||||||
Working pressure | Mpa | ≤0.35 | |||||||
Temperature Range | 45-65 | ||||||||
Power Supply | 50Hz 380V 3-Phase 4-Wire | ||||||||
Total Power | KW | 18+2.25 | 30+6 | 2X30+6.6 | 3X30+8.2 | 4X30+10 | 5X30+16.5 | ||
Inlet/Outlet Diameter | mm | 32 / 25 | 38 / 32 | 44 / 38 | 48 / 44 | 64 / 48 | 76 / 64 | ||
Size | Length | mm | 1200 | 1500 | 1870 | 1930 | 2160 | 2250 | |
Width | mm | 950 | 1150 | 1250 | 1400 | 1600 | 1750 | ||
Height | mm | 1600 | 2000 | 2200 | 2460 | 2650 | 2650 | ||
Weight | Kg | 650 | 900 | 1200 | 1600 | 2200 | 3000 | ||
Oil treatment index | Breakdown Voltage | KV | 70-75 | ||||||
Water Content | ppm | 3~5 | |||||||
Gas Content | % | ≤0.2 | |||||||
Filtration accuracy | µm | ≤1~3 |
Packaging Detail:Iron case |
Delivery Detail:within 30 to 45 days |