IP23 220VAC Top Mounted Industrial Electric Cabinet Air Conditioner for telecom cabinet
Condition:New | Type:Cabinet Air Conditioner | Place of Origin:Jiangsu China (Mainland) | Brand Name:Langji |
Model Number:SAT135, SAT-130 | Operating Voltage:Other | Mounting:top mounting | Certification:CE |
After-sales Service Provided:No overseas service provided | Rated Voltage:220VAC±15% 50/60Hz | Cooling Working Temperature:+20~+55 Degrees Celsius | Heating Working Temperature:-40~+15 Degrees Celsius |
Cooling Capacity:3000/3500W | Refrigerant:R134a | Weight:57/66Kgs | Noise:69dB |
Color:RAL7035 | IP Grade:IP23 | Dimension(W*H*D):950*395*420mm |
Top Mounting Industrial Cabinet Air Conditioner
Features :
- Cooling capacity: 3000W, 3500W
- Refrigerant: R134a
- Digital control mode, can reach high accuracy.
- The unit can work perfectly from -40 to +55 Degrees Celsius.
- Keep the dust, oil fog and moisture from entering the internal of the equipments. IP23
- The structure design makes the installation more flexible. And the unit can be installed perfectly in the side or outside wall of the equipment
- The protective level of internal and external circulation is IP55, which can protect cabinet to avoid moisture, dust, water and also it can be installed inside and outside.
- Digital temperature controlled and high precision of temperature control.
- Unique condensate treatment system, no condensate discharge.
- High reliability, long-term stable operation and can run at high ambient environment of 65°C.
- Automatic self start after power recovery.
- This series product can be used for enclosed area climate control such as wireless communication cabinet, battery cabinet, industry control cabinet etc.
- Totally solve dust and moisture contamination issues caused by ventilation.
- Widely used in telecommunications, broadcasting, electricity, automation and other industries out-door cabinet, IDC room cooling needs.
- The unit applications: electric equipment control box, battery compartment, and telecommunication equipment and other pertinent equipments, enclosed area climate control such as wireless communication cabinet, battery cabinet, industry control cabinet etc.
Installation instruction:
- Don't use the equipment in the environments with more dust, oil moisture, corrosive or harsh air. Among them shall not exceed 55°C ambient temperature, and not lower than 0°C, humidity should not exceed 95%.
- Use M6*10 screws fix flange on cabinet.
- Drain cannot stress, after the installation must ensure smooth condensate drain.
- Handling or moving the equipment , do not upside down, tilt and collision.
Design Diagram:
Parameter Table:
Application:
Related Products:
Certification:
How to Determine Correct Model of Cabinet cooler
Key Point---Calculating Heat Load for your Enclosure
To determine the correct model for your application, it is first necessary to determine thetotal heat loadto which the control panel is subjected. This total heat load is the combination of two factors — heat dissipated within the enclosure and heat transfer from outside into the enclosure.
Steps of Calculating Btu/hr.:
1. First, determine the approximate watts of heat generated within the enclosure. Watts x 3.41 = Btu/hr.
2. Then, calculate outside heat transfer as follows:
a. Determine the area in square feet exposed to the air, ignoring the top of the cabinet.
b. Determine the temperature differential between maximum surrounding temperature and desired internal temperature. Then, using the Temperature Conversion Table (below), determine the Btu/hr./ft.2for that differential. Multiplying the cabinet surface area times Btu/hr./ft.2provides external heat transfer in Btu/hr.
3. Add internal and external heat loads to get total heat load.
Temperature Conversion Table | |
Temperature Differential ° F | Btu/hr/ft.2 |
5 | 1.5 |
10 | 3.3 |
15 | 5.1 |
20 | 7.1 |
25 | 9.1 |
30 | 11.3 |
35 | 13.8 |
40 | 16.2 |
Example: Internal heat dissipation: 650 Watts or 2216 Btu/hr. Cabinet area: 40 ft.2 Maximum outside temperature: 110°F Desired internal temperature: 95°F The conversion table (above) shows that a 15°F temperature differential inputs 5.1 Btu/hr./ft.2 40 sq. ft. x 5.1 Btu/hr./ft.2= 204 Btu/hr. external heat load. Therefore, 204 Btu/hr. external heat load plus 2216 Btu/hr. internal heat load = 2420 Btu/hr. total heat load or Btu/hr. refrigeration required to maintain desired temperature. In this example, the correct choice is a 2500 Btu/hr. Cabinet Cooler System. |