Intelligent Motor Protector
Place of Origin:Guangdong China (Mainland) | Brand Name:YADA | Model Number:YD2310 |
Intelligent Motor Protector
Feature
Model | Structure | Function & Feature |
YD2301T | Integrated | ² The motor protector replaces the thermal relay protection by adopting Normal Close Contact Output. ² The running of the protected motor will not be interrupted when the protector stopped due to power failure. ² RS485 module is optional. |
YD2302T | The display part and the controlling part are separated | |
YD2301L | Integrated | ² Multiple startup modes are available; current protection; ² RS-485 communication; ² One route DC4-20mA output (optional). |
YD2302L | The display part and the controlling part are separated | |
YD2301C | Integrated | ² Multiple startup modes are available; current and voltage protection; ² One route DC4-20mA output (optional); ² RS-485 port. |
YD2302C | The display part and the controlling part are separated | |
YD2310 | The display part and the controlling part are separated | ² Universal protections and measuring; ² 4-20mA(or thermal resistance) input; ² Real-time clock; ² 1~19 harmonics analysis; ² Two routes of RS-485 ports; ² One route of DC4-20mA output(optional) |
Model Description
YD23 | |||||
Model | Rated Current | Controlling Mode | Code | Additional Function | Code |
YD2301T | 1A | Direct Startup | 4-20mA Output | M1 | |
YD2302T | 5A | Two-way Startup | Thermal protection | T | |
YD2301L | 10A | Y/ Startup | Leakage Protection | L | |
YD2302L | 50A | Autotransformer Step-down Startup | 4-20mA Input | M2 | |
YD2301C | 100A | Note: a. Functions with only applicable for YD2310; b. Built-in current transformer is used for rated current not more than 100A; independent specialized current transformer is needed when rated current is over 100A; Output current of CTs the secondary side is 1A. | |||
YD2302C | 250A | ||||
YD2310 | 500A | ||||
820A |
Specification
Parameters of performance | |
Rated Working Voltage | AC380V/660V, 50Hz |
Rated Working Current | 1A0-1A, 5A1A-5A, 10A1A-10A, 50A10A-50A, 100A50A-100ABuilt-in CT; 250A100A-250A, 500A250A-500A, 820A250A-820AIndependent CT |
Power supply | AC85V-265V, 50Hz or DC85V-330V |
Capacity of Relay Output Contact | AC250V 5A |
Accuracy | |
Current | ±1.0%≤120%Ie, ±3.0%120%Ie~800%IeYD2301/YD2302 |
±0.5%≤120%Ie, ±2.0%120%Ie~800%IeYD2310 | |
Voltage | YD2301C/YD2302C±1.0%, YD2310±0.5% |
Frequency | ±0.05HzYD2310 |
Power Factor | ±1%YD2310 |
Power | ±1%YD2310 |
Energy | ±1%YD2310 |
Electric Insulation Resistance | |
Insulation Resistance | 100MΩ/500V |
Insulation for Medium Intensity | 2kvr.m.s, 50Hz, 1min |
Working Conditions | |
Operating Conditions | Temp: -1055, 20%RH-95%RH |
Storage Conditions | Temp: -2570, 20%RH-95%RH |
Atmospheric Pressure | 80kPa∼110kPaRelative altitude less than 2KM |
Electro-magnetic Compatibility | |
Electrostatic Discharge | Electrostatic Discharge Test GB/T 14598.14idt IEC60255-22-2: Class Contact discharge: 8kV |
Radiated, Radio- frequency, Electromagnetic field Immunity | Radiated, Radio- frequency, Electromagnetic field Immunity Test GB/T 14598.10idt IEC60255-22-4: Class 40db μV/m |
Electrical Fast Transient Burst Immunity | Electrical Fast Transient Burst Immunity Test GB/T 14598.10idt IEC60255-22-4: Class Communication Port: 2 kV, other ports: 4kV |
Surge (Impulse) Voltage | Standard Lightening Wave Impulse Voltage Test GB/T 14598.3-1993eqv IEC60255-5: Peak value: 4kVheavy currentor 1kVweak current |
Packaging Detail:CTN |
Delivery Detail:7 days |