400W IP23/IP55 energy-saving industrial cabinet air conditioning unit

cabinet air conditioner, 1.Long service life, 2.High stability and efficiency, 3.Competitive price - details see: https://www.machineto.com/400w-ip23-ip55-energy-saving-industrial-cabinet-air-conditioning-unit-10222626
Condition:NewType:Cabinet Air ConditionerPlace of Origin:Jiangsu China (Mainland)Brand Name:Langji
Model Number:SAD104-1Operating Voltage:220VACMounting:door mountCertification:CE
After-sales Service Provided:Engineers available to service machinery overseasRated Voltage:220VACd15% 50/60HzCooling Working Temperature:+20~+55 Degrees CelsiusHeating Working Temperature:-40~+15 Degrees Celsius
Cooling Capacity:400WRefrigerant:R134aWeight:18.5 KgsNoise:62dB
Color:RAL7035IP Grade:IP23/IP55Dimension(W*H*D):470*788*185mm 
400W IP23/IP55 energy-saving industrial cabinet air conditioning unit
contact supplier for 400W IP23/IP55 energy-saving industrial cabinet air conditioning unit


Door Mounting Cabinet Air Conditioner

Scope:

1.Widely used in telecommunications,broadcasting,electricity,automation and other industries outdoor cabinet,IDC room cooling needs.

2.Applications:electric equipment control box,battery compartment,and telecommunication equipment and other pertinent equipments,enclosed area climate control such as wireless communication cabinet,battery cabinet,industry control cabinet etc.

Features:

1.Applicable for severe ambient environment,such as high temperature.

2.Can work perfectly from -40 to +55 Degrees Celsius.

3.Using natural cooling technologies,energy efficient operation.

4.Keep dust,oil fog and moisture from entering the internal of the equipments.Totally solve dust and moisture contamination issues caused by ventilation.

5.Flexible installation,can be installed perfectly in the side or outside wall of the equipment.

Technique Data Sheet:

Installation Instruction:

1.Don't use the equipment in the environments with more dust, oil moisture, corrosive or harsh air. Among them shall not exceed 55°C ambient temperature, and not lower than 0°C, humidity should not exceed 95%.

2.Use M6*10 screws fix flange on cabinet.

3.Drain cannot stress, after the installation must ensure smooth condensate drain,handling or moving the equipment,do not upside down, tilt and collision.

Installation Picture:

Application:

Related Products:

How to Determine Correct Model of Cabinet cooler

Key Point---Calculating Heat Load for your Enclosure
To determine the correct model for your application, it is first necessary to determine thetotal heat loadto which the control panel is subjected. This total heat load is the combination of two factors — heat dissipated within the enclosure and heat transfer from outside into the enclosure.

Steps of Calculating Btu/hr.:
1. First, determine the approximate watts of heat generated within the enclosure.Watts x 3.41 = Btu/hr.

2. Then, calculate outside heat transfer as follows:
a. Determine the area in square feet exposed to the air,ignoring the top of the cabinet.
b. Determine the temperature differential between maximum surrounding temperature and desired internal temperature. Then, using the Temperature Conversion Table (below), determine the Btu/hr./ft.2for that differential. Multiplying the cabinet surface area times Btu/hr./ft.2provides external heat transfer in Btu/hr.

3. Add internal and external heat loads to get total heat load.

Temperature Conversion Table

Temperature
Differential ° F
Btu/hr/ft.2
51.5
103.3
155.1
207.1
259.1
3011.3
3513.8
4016.2


Example:
Internal heat dissipation: 650 Watts or 2216 Btu/hr.
Cabinet area: 40 ft.2
Maximum outside temperature: 110°F
Desired internal temperature: 95°F
The conversion table (above) shows that a 15°F temperature differential inputs 5.1 Btu/hr./ft.2

40 sq. ft. x 5.1 Btu/hr./ft.2= 204 Btu/hr. external heat load.

Therefore, 204 Btu/hr. external heat load plus 2216 Btu/hr. internal heat load = 2420 Btu/hr. total heat load or Btu/hr. refrigeration required to maintain desired temperature.
In this example, the correct choice is a 2500 Btu/hr. Cabinet Cooler System.

More details,contact us!

400W IP23/IP55 energy-saving industrial cabinet air conditioning unit
Packaging Detail:1 PC/Carton with foam
Delivery Detail:25 Days After Deposit or L/C

Related Product for 400W IP23/IP55 energy-saving industrial cabinet air conditioning unit