250W/K heat exchanger telecom
heat exchanger telecom, cooling capacity: 40-350W/K., heat pipe technology, IP55 grade, AC/DC power supply - details see: https://www.machineto.com/250w-k-heat-exchanger-telecom-10241545
Condition:New | Place of Origin:Jiangsu China (Mainland) | Brand Name:HPT | Model Number:HHh-250 |
Structure:heat pipe heat exchanger | Certification:CE,ROHS |
heat exchanger telecom
Scope:
- Widely used in telecommunications, broadcasting, electricity, automation and other industries out-door cabinet, IDC room cooling needs.
- Using natural cooling technologies, energy efficient operation, more reliable than air-conditioning, lower cost.
- Completely solved dust and moisture contamination issues caused by ventilation.
Feature:
- AC,DC optional for various application
- Heater is optional
- Multiple protection features
- Alarm output to monitoring system
- Interchangeable and visual display service adapter
- Automatic self start after power recovery
- Remote control through RS485 comm. port
- Speed controller for AC,DC models reduces noise, increases life, saves energy
- Integration of superconducting heat-pipe technology and micro-channel heat exchanger technology,the performance is excellent
- Proper design for easily installation and service
Datasheet
1> 40W/K - 100W/K as below:
Items | Unit | Description | Models | |||
HHh-040 | HHh-060 | HHh-080 | HHh-100 | |||
Cooling Capacity | W/K | 40 | 60 | 80 | 100 | |
Heater | W | Optional | 300 , 500 | 500 , 800, 1000 | ||
Air Flow | m3/h | Internal air flow | 240 | 360 | 490 | 620 |
Fan type | Backward Centrifugal Fan | |||||
Temp. | °C | Operating range | -40 ~ 60°C 0 ~ 90% RH | |||
Noise | dB(A) | 3m,away ETS300-753 | 50 | 52 | 55 | 55 |
Dimension | mm | W*H*D | 320*800*150 | 425*1122*150 | ||
Weight | Kg | Net Weight | 12 | 13.5 | 21 | 22 |
Power Consumption | W | DC: 48V | 62 | 87 | 122 | 131 |
AC: 230V/110V | 78 | 96 | 143 | 154 | ||
Power Supply | V | Rated | 48VDC, 230VAC/110VAC, 50/60Hz | |||
IP | IEC6052 | >= IP55 |
2> 120W/K - 250W/K as below:
Items | Unit | Description | Models | |||
HHh-120 | HHh-150 | HHh-200 | HHh-250 | |||
Cooling Capacity | W/K | 120 | 150 | 200 | 250 | |
Heater | W | Optional | 500 , 800, 1000 | 800, 1000,2000 | ||
Air Flow | m3/h | Internal air flow | 720 | 920 | 1200 | 1500 |
Fan type | Backward Centrifugal Fan | |||||
Temp. | °C | Operating range | -40 ~ 60°C 0 ~ 90% RH | |||
Noise | dB(A) | 3m,away ETS300-753 | 57 | 57 | 58 | 58 |
Dimension | mm | W*H*D | 450*1172*200 | 550*1572*220 | ||
Weight | Kg | Net Weight | 24 | 25 | 37 | 39 |
Power Consumption | W | DC: 48V | 148 | 157 | 200 | 210 |
AC: 230V/110V | 170 | 185 | 227 | 246 | ||
Power Supply | V | Rated | 48VDC, 230VAC/110VAC, 50/60Hz | |||
IP | IEC6052 | >= IP55 |
Packaging Detail:Inner: environmental PE bag, Outer:wooden case |
Delivery Detail:3-4weeks |