Technical feature
(1) The machine is designed for the super HV transformer oil, particularly for the oil treatment that over 750KV power distribution system.
(2) The machine chose LATENT technology to dewater and degas, could efficiently remove the water and gas from the insulation oil, increase the breakdown voltage over 80 KV. The water content is less than 3 PPM.
(3) The shunt branch node, rapid evaporation of the oil in the water. Insulating oil in the system is fully distributed and spray film (an increase of insulating oil atomization in a vacuum area), and greatly increased the limits of the oil in the system's "path", so that the oil in the Water and gas vaporization of time sufficient to achieve the best effect of dehydration degassing. Full scan using patented infrared liquid level and foam control system, avoiding any mechanical movement, improve equipment reliability, the system is maintenance-free system.
(4) Patent filtration system - potential (QIANNENG) patented technology, using a special polymer composite filter of the United States, "getting close"type filter, filter rate 100 times the effective removal of oil particles, while the life of the filter Also greatly improved. Encrypted using gradual, proportional share of the impurity levels of filter loading, and using reasonable to ensure the cleanliness of the fluid design of the realization of the oil filter depth of fine particles. Also uses electrostatic adsorption, can not easily be removed so that the negative charge carriers, so that the adsorption and the positive charge, to charge balance, which is more thoroughly to remove impurities, the effective index requirements to ensure that high oil. Filtering accuracy (less than NAS2 grade) particle size ≤ 900/100ml (5μm or more particles)
(5) The breakdown voltage could be over 80KV, water content is 3 PPM for one-time treatment. Acetylene is zero.
(6) The machine equipped the on-line temperature inspector, voltage tester, vacuum tester, oil level inspector, could know the oil condition and equipment working condition anytime.
Use
To be used for treatment to new oil, working oil, particularly applicable to 220KV-1000KV power distribution system and the national grid, shortening the oil treating duration during installation and maintenance of transformer. Meet the national grid of 750-1000KV power transformers, oil immersed reactors, transformer construction and acceptance(Q/GDW 122-2005).
Items | Unit | ZJA-50 | ZJA-100 | ZJA-150 | ZJA-200 | ZJA-250 | ZJA-300 | |
Flow | L/min | 50 | 100 | 150 | 200 | 250 | 300 | |
Working vacuum | pa | ≤133 | ||||||
Limited vacuum | pa | ≤5 | ||||||
Working pressure | Mpa | ≤0.4 | ||||||
Temperature range | °C | 20 ~80 | ||||||
Power | 380V 50HZ(at user's option) | |||||||
Noise | dB(A) | ≤65~80(at user's option) | ||||||
Fault-free working hour | h | ≥4000 | ||||||
Continuing working hour | h | ≥150 | ||||||
Heating power | Kw | 72 | 120 | 144 | 192 | 240 | 288 | |
Total Power | Kw | 78 | 130 | 155 | 215 | 260 | 305 | |
Inlet(outlet) diameter | mm | Φ32 | Φ42 | Φ50 | Φ50 | Φ60 | Φ60 | |
Weight | kg | 850 | 1000 | 1350 | 1850 | 2200 | 2500 | |
After filtration | Breakdown voltage | KV | ≥80 | |||||
Water content | ppm | ≤3 | ||||||
Medium Consumption | tgδ(90°C)% | ≤0.1 | ||||||
Acid value | mgKOH/g | ≤0.03 | ||||||
Gas content | % | ≤0.1 | ||||||
Particle | particle/100ml | ≤900(≥5μm)customer’s requirment |
Packaging Detail:wooden case |