Maneurop Hermetic Compressor Condensing Unit MT100
Type:Condensing Unit,semi hermetic | Place of Origin:Guangdong China (Mainland) | Brand Name:Maneurop | Model Number:MT 100 |
Certification:CE,CCC | After-sales Service Provided:No overseas service provided | color::blue | Usage:Fruits, vegetables, meat, beer |
Temperature:-40~+35celsius | Configuration:Stationary | Power Source:AC Power Lubrication | Voltage:380V/50HZ |
Gas:22 R404 R507 | Horse Power:15HP | Weight:120kg |
Specifications
1.air cooled compressor condensing refrigeration equipment
2. good quality, reliable operation
HERMETIC CONDENSING UNIT
RANGE OF APPLICATION
1.refrigeration industry,cold room project
2.Agriculture,food, restaurant,chemical industry
3.We offer customized design and services
The Condensing Units are prefabricated, monoblock type, factory tested and easy to mount on Cold Room’s wall. The built-in electronic control panel with the microprocessor allows for manual setting of the desired temperature. It has the following components:
*An On-Off button for switching the unit on and off
*An On-Off Lighting button
*Three buttons for Temperature Setting
*A Manual Defrosting button
*A Digital Display showing the current room temperature.
All Condensing Units can be equipped with different kinds of refrigerants according to the clients' requirements.
Technical Data:
Technical Data | Model | |||||||||||||||||||||
FPMT -18 | FPMT -22 | FPMT -28 | FPMT -32 | FPMT -36 | FPMT -40 | FPMT -50 | FPMT -64 | FPMT -80 | FPMT -100 | FPMT -125 | FPMT -144 | FPMT -160 | ||||||||||
Compressor Model | MT 18 | MT 22 | MT 28 | MT 32 | MT 36 | MT 40 | MT 50 | MT 64 | MT 80 | MT 100 | MT 125 | MT 144 | MT 160 | |||||||||
Titular Refrigeration Capacity (W) | 1864 | 2713 | 3947 | 4219 | 5062 | 5515 | 6217 | 8172 | 10340 | 12167 | 16199 | 18339 | 20344 | |||||||||
Compressor Rated Input Power (KW) | 1.45 | 1.89 | 2.55 | 2.98 | 3.37 | 3.85 | 4.32 | 5.66 | 7.13 | 7.98 | 10.66 | 11.95 | 13.39 | |||||||||
Compressor Rated Input Current (A)1 | 2.73 | 3.31 | 4.56 | 4.97 | 5.77 | 6.47 | 8.46 | 9.54 | 11.58 | 14.59 | 17.37 | 22.75 | 22.16 | |||||||||
Compressor Max. Continuous Current (A) | 5/12 | 6/15 | 7.5/16 | 8/20 | 9/20 | 10 | 12 | 15 | 18 | 22 | 27 | 30 | 36 | |||||||||
Refrigerant | R22 | |||||||||||||||||||||
Power | 400V-3PH-50Hz/230V-1PH-50Hz | 400V-3PH-50Hz | ||||||||||||||||||||
Power of Crankcase Heater (W) | 54W, belt type crankcase heater | 50W, belt type crankcase heater | 75W, belt type crankcase heater | |||||||||||||||||||
Power of Condensing Fan Motor (W) | 90 | 90 | 120 | 120 | 120 | 90/120×2 | 90/120×2 | 120×2 | 120×2 | 120×2 | 120×4 | 120×4 | 120×4 | |||||||||
Fan Motor Working Current (A) | 0.2 | 0.2 | 0.3 | 0.3 | 0.3 | 0.2/0.3×2 | 0.2/0.3×2 | 0.3×2 | 0.3×2 | 0.3×2 | 0.3×4 | 0.3×4 | 0.3×4 | |||||||||
Rate of Evaporating Temperature | from 0oC to -20oC |
Air-cooled Condensing Unit, including:
1. 1 PCS of Compressor
2. 1 PCS of Receiver tank
3. 1 PCS of Oil separator
4. 1 PCS of High presure protector
5. 1 PCS of Dier Filter
6. 1 PCS of Solenoid valve
7. 1 PCS of Condenser
8. 1 PCS of Oil gauge
9. 1 PCS of Gauge floor
10.1 PCS of High Pressure gauge
11.1 PCS of Low Pressure gauge
12.1 PCS of Expansion Valve
13.1 PCS of Oil Pressure protector
Packaging Detail:Export packing |
Delivery Detail:10days |